Gree GMV6 DC Inverter VRF Units Service Manual
79
Yes
No
No
"b1" Outdoor Ambient
Temperature Sensor Fault
Whether th e i nter face
terminal between the main boa rd and
temperature sensor gets loose or
contains foreign matters?
Remove the foreign
matters and plug it tightly
Whether th e temperature
sensor is abn ormal?
Yes
Replace th e temperature
sensor
The detection circuit may
operate impro perly
Yes
Replace th e main control
board
2.18 "b2" Defrosting Temperature Sensor 1 Fault
Fault display: main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display
Fault diagnosis:
The temperature sensor detection circuit samples the AD value of temperature sensor and
determines the range of AD value. When the sampled AD value exceeds the limits for 30 consecutive
seconds, the fault is generated.
Possible causes:
Poor contact between the temperature sensor and the main board interface;
Abnormal temperature sensor;
Abnormal detection circuit.
Troubleshooting:

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV6 Series and is the answer not in the manual?

Gree GMV6 Series Specifications

General IconGeneral
BrandGree
ModelGMV6 Series
CategoryInverter
LanguageEnglish

Related product manuals