95
GMV6 DC Inverter VRF Units Technical Sales Guide
TC—Total capacity of outdoor unit; PI—Power input of outdoor unit
combination
outdoor air
temp
indoor air temperature
℃
DB
16 18 20 21 22 24
TC PI TC PI TC PI TC PI TC PI TC PI
℃
DB
℃
WB kW kW kW kW kW kW kW kW kW kW kW kW
50%
-19.8 -20 40.1 29.63 37.5 27.33 34.8 24.47 33.6 23.74 32.2 22.73 30.1 21.13
-18.8 -19 40.1 29.01 37.5 26.79 34.8 24.02 33.6 23.26 32.2 22.28 30.1 20.72
-16.7 -17 40.2 27.71 37.6 25.60 34.9 23.00 33.6 22.30 32.2 21.38 30.1 19.86
-13.7 -15 40.2 26.43 37.6 24.44 34.9 21.97 33.7 21.32 32.3 20.44 30.1 18.97
-11.8 -13 40.2 25.10 37.6 23.27 34.9 20.93 33.7 20.30 32.3 19.45 30.1 18.07
-9.8 -11 40.3 23.81 37.7 22.05 35.0 19.91 33.7 19.30 32.4 18.52 30.1 17.17
-9.5 -10 40.3 23.17 37.7 21.46 35.0 19.41 33.8 18.83 32.4 18.05 30.1 16.73
-8.5 -9.1 40.3 22.59 37.7 20.96 35.0 18.93 33.8 18.38 32.4 17.63 30.1 16.35
-7 -7.6 40.2 21.61 37.6 20.13 34.9 18.15 33.7 17.63 32.3 16.91 30.1 15.72
-5 -5.6 40.0 20.27 37.4 18.84 34.7 17.09 33.5 16.60 32.3 16.02 30.1 14.90
-3 -3.7 40.0 19.19 37.4 17.85 34.7 16.21 33.5 15.74 32.3 15.19 30.1 14.17
0 -0.7 40.0 17.62 37.4 16.39 34.7 14.95 33.5 14.51 32.3 14.03 30.1 13.10
3 2.2 40.0 16.22 37.4 15.12 34.7 13.79 33.5 13.41 32.3 12.99 30.1 12.13
5 4.1 40.0 15.40 37.4 14.34 34.7 13.11 33.5 12.76 32.3 12.34 30.1 11.54
7 6 40.0 14.61 37.4 13.63 34.7 12.50 33.5 12.14 32.3 11.75 30.1 11.02
9 7.9 40.0 13.86 37.4 12.96 34.7 11.88 33.5 11.59 32.3 11.20 30.1 10.50
11 9.8 40.0 13.18 37.4 12.32 34.7 11.33 33.5 11.04 32.3 10.68 30.1 10.01
13 11.8 40.0 12.54 37.4 11.71 34.7 10.79 33.5 10.52 32.3 10.16 30.1 9.56
15 13.7 40.0 11.93 37.4 11.18 34.7 10.30 33.5 10.04 32.3 9.71 30.1 9.11
18 16.8 40.0 11.35 37.4 10.68 34.7 9.89 33.5 9.62 32.3 9.30 30.1 8.69
20 18.5 40.0 10.82 37.4 10.22 34.7 9.51 33.5 9.28 32.3 8.92 30.1 8.31
24 20.5 40.0 10.32 37.4 9.80 34.7 8.86 33.5 8.96 32.3 8.57 30.1 7.96
6.2 Capacity rectification for piping length and fall