Chapter Product Introduction3. Basic Parameters of Unit
4
3. Basic Parameters of Unit
Model
GRS-Cm28/NaA-M
GRS-Cm28/NaA1-M
GRS-Cm36/NaA-M
GRS-Cm36/NaA1-M
GRS-Cm53/NaA-M
GRS-Cm53/NaA1-M
Product Code
ER01000150
ER01000180
ER01000160
ER01000190
ER01000170
ER01000200
Hot water
mode
Heating capacity
kW
28
36
53
Heating Power Input
kW
7.3
9.3
13
Heating Current Input
A
13.9
16.9
26
Nominal Water Output
L/h
602
775
1140
Rated Input
kW
10.1
13.2
19
Rated current Input
A
20
24
38
Set temperature
defaulted at 50. 30℃~60 adjustable (water tank temperature)
Power
380-415V 3N50Hz
Refrigerant
Name
R410A
R410A
R410A
Refrigerant charge
volume
kg
4.2
4.2
5.9
Compressor
Type
Totally-enclosed scroll compressor
Q‟ty
Set
1
1
1
Heat
exchanger
Wind side
Finned type heat exchanger
Water side
Shell-and-tube heat exchanger
Fan
Type
Low noise axial flow fan
Air discharge type
Top air discharge
Airflow(ambient
temperature 25)
m
3
/h
11400
11400
12400
Water system
Circulating Water
Flow
m
3
/h
4.8
6.2
9.2
Water pressure
kPa
70
130
70
Maximum bearing
pressure
MPa
0.8
0.8
0.8
Diameter of air inlet
pipe and air outlet
pipe
in
G 1-1/4
G 1-1/4
G 2
Outline
dimension
W×H
mm
930×800×1605
930×800×1605
1340×800×1605
Packing size
W×H
mm
1010×865×1775
1010×865×1775
1420×880×1775
Noise
dB(A)
≤67
≤67
≤67
Unit net weight
kg
243242
260262
358364
Data in the above table are based on the following test conditionsoutdoor ambient
temperature: 20 DB/15 WB; initial water temperature: 15; final water temperature:55℃;
Voltage: 380V 3N50Hz.
Applicable range: ambient temperature range is -26°C~46°C.
The above pressure values all belong to gauge pressure.
Noise is tested in the semi-silencing room. The actual noise will be a little higher in the