Chapter Maintenance3. Maintenance of Key Parts
71
2Take off
the fixing nuts of
tube in tube
condenser and
then remove the
tube in tube
condenser.
Take off the fixing nuts
by using a spanner or
other tools;
Remove the tube in
tube condenser from the
base plate.
3Replace
with a new tube
in tube
condenser and
then secure the
nuts.
● Install the new tube in
tube condenser on the
base plate;
● Use a spanner to
tighten up the fixing nuts
of tube in tube
condenser;
Weld the fluorine
connection pipe and
tighten the waterway
conenction pipe.
4 Reclam
system
pressure,
vacuumize and
recharge
refrigerant.
——
● Detect system
leakage;
● Make sure the vacuum
degree reaches -1.0bar;
Type and amount of
refrigerant should accord
with requirements on
unit‟s nameplate.
3.2.1.4 Electronic expansion valve
Removal/ Installation of electronic expansion valve
Remarks: Check the refrigerant system and each circuit. After making sure that it is necessary
to replace electronic expansion valve, disconnect power and reclaim the refrigerant.