Chapter Maintenance3. Maintenance of Key Parts
75
3.2.1.6 Strainer
Removal/ Installation of strainer
Remarks: Check the refrigerant system and each circuit. After making sure that it is
necessary to replace the filter, disconnect power and reclaim the refrigerant.
Step
Figure
Operation Instructions
1
Reclaim the
refrigerant.
● Disconnect power
of the unit;
● Reclaim the
refrigerant.
2
Remove the
strainer.
● In order to protect
the EXV, wrap it with
wet cloth during
welding;
● Remove the filter by
using the soldering
gun.
3
Replace with
a new filter.
● Replace with a new
filter that is of the
same model;
Wrap the EXV with
wet cloth and mount
teh filter on. Connect
the connection pipe;
Weld it with
soldering gun;
Note: Add nitrogen
into the pipe when
welding.
4Retain
system
pressure,
vacuumize
and recharge
refrigerant.
——
Detect system
leakage;
● Make sure the
vacuum degree
reaches -1.0bar;
● Type and amount of
refrigerant should
accord with
requirements on unit‟s
nameplate.