U-Match Series Duct Type Unit
40
GU100W/A1-M, GU125W/A1-M ,GU140W/A1-M, GU160W/A1-M.
GU100PH/A1-K;GU100PHS/A1-K+GU100W/A1-M
GU125PH/A1-K;GU125PHS/A1-K+GU125W/A1-M
GU140PH/A1-K;GU140PHS/A1-K+GU140W/A1-M
GU160PH/A1-K;GU160PHS/A1-K+GU160W/A1-M
.
Power cord 5×1.5mm
2
.
Power cord 3×1.0mm
2
.
Communication Cords 2×0.75mm
2
.
Communication Cords 2×0.75mm
2
(5) Electrical wiring of indoor unit.
WARNING
.
High and low voltage wires should be led through different rubber rings of the
electric box cover.
.
Do not bundle up the connection wire and communication wire of wired control
or lay them side by side, otherwise errors will occur.
.
High and low voltage wires should be secured separately. Secure the former
ones with big clamps and the latter ones with small clamps.
.
Use screws to tighten up the connection wires and power cords of indoor and
outdoor units on the terminal board. Wrong connection may lead to fire hazard.
.
If the connection wires of indoor unit (outdoor unit) and power cords are not
correctly connected, the air conditioner may get damaged.
.
Ground the indoor and outdoor units through connecting the ground wire.
.
The units should comply with applicable local and national rules and
regulations on power consumption.
Power:380V-415V 3N ~ 50Hz
Outdoor Unit
Indoor Unit
Wired
Controller
Power:220V-240V~ 50Hz
L2
L1 L3
N
2
1
2
1
H1
H2
breaker
breaker