U-Match Series Duct Type Unit
42
GU100W/A1-M, GU125W/A1-M, GU140W/A1-M, GU160W/A1-M
GU125W/A1-M, GU140W/A1-M, GU160W/A1-M
Power cord should be secured along with the right side plate and fixed to the
hook with a wire clamp so as to avoid contacting the pipeline. The communication
line between indoor and outdoor units should also be laid along with the right side
plate but away from the power cord.
3.4 Check after Installation
Check Items after Installation
Possible events due to improper installation
Is the main body installed
securely?
The unit may fall down, vibrate or produce
noise.
Did you do water leakage test?
Cooling capacity may become unsatisfactory.
Is the unit well insulated from
Condensate, water drops may occur.
Does water drainage go well? Condensate, water drops may occur.