GREE DC INVERTER HEAT PUMP CONDENSING UNIT SERVICE MANUAL
84
Removal of Front Panel
NOTE: Before removing the front panel, make sure power is cut off.
Step Picture Work Instruction
10. Install the upper cover plate.
Tighten up the screws
around the upper cover
plate.
Model:
GUD24W2/D-D(U), GUD30W2/D-D(U), GUD36W2/D-D(U)
Removal of Compressor
NOTE: Before removing the compressor, make sure there is no refrigerant in the pipeline and power is cut off.
Step Picture Work Instruction
1. Remove wires.
Loosen the securing
screws of the wires with a
screwdriver.
Remove the wires.
NOTE: When removing
the wires, mark the wire
terminals corresponding
to their color so as to
avoid misconnection.
2. Break off the pipes
that connecting to the
compressor.
Weld the pipes that are
connected to the
compressor.
Then remove the pipes.
NOTE: When welding the
pipes, do not let the flame
burn the other
components.