Method of Testing IPM Module Short Circuit:
1. Preparation before test: prepare a universal meter and turn to its diode option, and then remove the
wires U, V, W of the compressor after it is powered off for one minute.
2. Testing Steps
Step 1: put the black probe on the place P and the red one on the wiring terminal U, V, W respectively
DVVKRZQLQWKHIROORZLQJ¿JXUHWRPHDVXUHWKHYROWDJHEHWZHHQ8393DQG:3
Step 2: put the red probe on the place N and the black one on the wiring terminal U, V, W respectively
DVVKRZQLQWKHIROORZLQJ¿JXUHWRPHDVXUHWKHYROWDJHEHWZHHQ1819DQG1:
3. If the measured voltages between UP, VP, WP, NU, NV, NV are all among 0.3V-0.7V, then it indicates
the IPM module is normal; If any measured valve is 0, it indicates the IMP is damaged.
Ɣ
PFC or IPM module overheat
N
N
Y
Y