4
Outdoor 
condenser 
temperature 
sensor is open/ 
short-circuited
F4
The unit will stop 
operation as it reaches 
the temperature point. 
During cooling and drying 
operation, the compressor 
stops operation while IDU 
fan motor operates; During 
heating operation, the 
heating fan motor operates 
according to the conditions 
of blowing residual heat.
1. The wiring terminal between outdoor 
condenser temperature sensor and 
maiboard is loosened or poorly contacted;
Refer to Malfunction 
Detection Flowchart
2. There’s short circuit due to trip-over of 
the parts on maiboard;
3. Outdoor condenser temperature sensor 
is damaged (Please check it by referring 
to the resistance table for temperature 
sensor);
4. Mainboard is broken.
5
Outdoor 
discharge 
temperature 
sensor is open/ 
short-circuited
F5
The unit will stop 
operation as it reaches 
the temperature point. 
During cooling and drying 
operation, the compressor 
stops operation while IDU 
fan motor operates; During 
heating operation, the 
heating fan motor operates 
according to the conditions 
of blowing residual heat.
1. The wiring terminal between outdoor 
discharge temperature sensor and 
maiboard is loosened or poorly contacted;
Refer to Malfunction 
Detection Flowchart
2. There’s short circuit due to trip-over of 
the parts on maiboard;
3. Outdoor discharge temperature sensor 
is damaged (Please check it by referring 
to the resistance table for temperature 
sensor);
4. Mainboard is broken.
6
High pressure 
protection
E1
During cooling and drying 
operation, except IDU 
fan motor operates, all 
loads stop operation. 
During heating operation, 
the complete unit stops 
and operation of remote 
controller or buttons is 
unavailable.
1. The mainboard and the display board 
are not connected well;
Refer to Malfunction 
Detection Flowchart
2. The OVC terminal on mainboard is not 
connected well with the high pressure 
switch on the complete unit;
3. The wiring terminal between high 
pressure switch and maiboard is loosened 
or the high pressure switch is broken;
4. Refrigerant is superabundant;
5. Poor heat exchange (including blocked 
heat exchanger and bad radiating 
environment );
6. Ambient temperature is too high; (if it is 
3-phase unit, the high pressure protection 
may be caused by overcurrent protection 
due to this reason);
7. The supply voltage is abnormal (if it is 
3-phase unit, the high pressure protection 
may be caused by overcurrent protection 
due to this reason);
8. The air intake and air discharge at 
indoor / outdoor heat exchanger are not 
smooth;
9. Filter and heat exchange ns of indoor/
outdoor units are blocked;
10. The pipeline is blocked;
11. The gas valve and liquid valve for 
outdoor unit are not completely opened;
12. The OVC input is at high level.
7
Low pressure 
protection of 
compressor
E3 The complete unit stops.
1.The mainboard and display board are 
not connected well;
Refer to Malfunction 
Detection Flowchart
2. The LPP terminal on the mainboard is 
not connected well with the high pressure 
switch;
3. The wiring of high pressure switch 
is loosened or high pressure switch is 
damaged. 
4. The refrigerant is insufcient;
5. The LPP input is at high level.