EasyManuals Logo

Gree GVA48AL-M3NNC7A/I User Manual

Gree GVA48AL-M3NNC7A/I
95 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #53 background imageLoading...
Page #53 background image
Service Manual
50
Installation and Maintenance
7. High temperature and overload protection (AP1 below means control board of outdoor unit) E8
Main detection points:
● If the outdoor ambient temperature is in normal range;
● If the indoor and outdoor fan are running normally;
● If the radiating environment of indoor and outdoor unit is good.
Malfunction diagnosis process:
Start
If the outdoor ambient temperature is
higher than 53°C?
is good?
If the indoor and outdoor fan are
running normally?
Replace outdoor
mainboard
Connect normally?
Adjust the
connection
Replace fan
capacitor
Replace motor
Fan capacitor is broken?
Motor is broken?
Replace mainboard
Improve the radiating environment of
unit (clean the heat exchanger and
remove surrounding obstacles)
Normal protection, please use it
after improving the outdoor ambient
temperature
Unit restarts
normally
Unit restarts
normally
End
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GVA48AL-M3NNC7A/I and is the answer not in the manual?

Gree GVA48AL-M3NNC7A/I Specifications

General IconGeneral
BrandGree
ModelGVA48AL-M3NNC7A/I
CategoryAir Conditioner
LanguageEnglish

Related product manuals