17
Technical Information
Service Manual
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 24.6 ft.
Heating:
Rated heating condition(°F)
(DB/WB)
Model
Pressure of gas pipe connecting
indoor and outdoor unit
Inlet and outlet pipe temperature of
heat exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Indoor Outdoor PSIG T1 (°F) T2 (°F)
70/60 19.94/19.04
09K 362~406
in:167~181.4
out:98.6~113
in:33.8~37.4
out:35.6~42.8
Super High High
12K 362~406
in:167~181.4
out:98.6~113
in:33.8~37.4
out:35.6~42.8
18K 507~550
in:167~181.4
out:98.6~113
in:33.8~37.4
out:35.6~42.8
24K 507~550
in:167~181.4
out:98.6~113
in:33.8~37.4
out:35.6~42.8