47
Technical Information
Service Manual
(1) When Toutdoor amb.≤≤23ºF , compressor stops operation,
while the electric heating of compressor starts operation;
(2) When Toutdoor amb.>28.4ºF , the electric heating of
compressor stops operation;
(3) When 23ºF <Toutdoor amb.≤28.4ºF , the electric heating of
compressor will keep original status.
6. Electric Heating Function of Chassis
(1) When Toutdoor amb.≤32ºF , the electric heating of chassis will
operate;
(2) When Toutdoor amb.>35.6ºF , the electric heating of chassis
will stop operation;
(3)When 32ºF <Toutdoor amb.≤35.6ºF, the electric heating of
chassis will keep original status.
7. Electric Heating Function of Compressor
(1) When Toutdoor amb.≤≤23ºF , compressor stops operation,
while the electric heating of compressor starts operation;
(2) When Toutdoor amb.>28.4ºF , the electric heating of
compressor stops operation;
(3) When 23ºF <Toutdoor amb.≤28.4ºF , the electric heating of
compressor will keep original status.