When the touch screen is shielded, Shield Touch Screen! Invalid Setting! will be
shown on the right side of the interface. In that case, each setting interface is read-only and its
parameter setting cannot be revised.
2Module Mode Setting
Slightly press the button “Module Setting” to enter the interface of “Module Mode Setting
Only when unit is set off on the homepage can the mode setting of each module be
effective on this interface.
Link/Break”: When the connection is set, the module is connecting with and controlled
by the main module; When the disconnection is set, the communication breaks and the module
is out of control. At that time, related units are auto turned off which will be turned on by setting
connection and the data of the unit on the touch screen shows 0.
ON/OFF”: It means the unit of the module in the ON/OFF state.
Entire/ Alone”: When the entire running is set, the module will be running together with
the other entire modules, including alternate running, standby running; When the Alone running
is set, the module will be running alone. Temp. and humidity is Subject to the unit itself without
functions of alternation and standby.
Auto/Manual”: When “manual” is displayed, the module is in the manual operation state.
By touching it, the state will switch to auto running. But the reverse setting should be set in the
Parameter Setting Manual Debugging.” In addition, if “entire” is set, manual mode is
shielded.(Default to auto)
Duty Time”: It means the alternately continuous running time of the entire running state of
modules and the setting time range is 1~720 hours. Default time range is 96 hours. When the
accumulated running time of the module has been reached the preset time for alternate running,
the module will stop and the other standby module will start in order to make each module run
in turn.
Standby Units”: It means the standby units of modules stopped. Only the modules which
are set to states of Link, ON, Entire running would be set to standby. When the Qty is 0, there
are no functions of alternation and standby; when the standby units are bigger or equal to the