S2S KNX Gateway
21
Object# 7
Name Vanes R-L Swing – Control
Function
Control the ON/OFF of left and right swing of air
conditioner
Description
Message “1”: ON
Message “0”: OFF
Read/Write Write
Type of data point 1 bit
Object# 8
Name Setpoint Temperature – Control
Function Set the temperature of air conditioner
Description
Transmission value = actual value, actual value:
16.0~30.0
Read/Write Write
Type of data point 2 byte
Object# 9
Name Lower limit Temp. of Cool energy saving – Control
Function
Set the lower cooling temperature limit of air
conditioner
Description
Transmission value = actual value, actual value:
16.0~30.0;Reserved.
Read/Write Write
Type of data point 2 byte