S2S KNX Gateway
24
Object# 16
Name Fan Speed – Status
Function
Feed back the fan speed status of the current air
conditioner
Description
01: fan stops; 02: ultra-low; 03: low; 04: medium and
low; 05: medium; 06: medium and high; 07: high; 08:
ultra-high
Read/Write Read
Type of data point 1 byte
Object# 17
Name Mode – Status
Function
Feed back the operating status of the current air
conditioner
Description
01: cooling; 02: dehumidifying; 03: air supply;
04:heating; 05: auto cooling; 06: auto heating; 07:
oor heating; 08: 3D heating; 09: space heating
Read/Write Read
Type of data point 1 byte