S2S KNX Gateway
25
Object# 18
Name Setpoint Temperature – Status
Function
Feed back the set temperature of the current air
conditioner
Description
Transmission value = actual value, actual value:
16.0~30.0
When it reads 8
, it means the unit has activated the
8
heating function;
When it reads 12
, it means the unit has activated
the low-temperature dehumidifying function.
When 8
heating or low-temperature dehumidifying
are activated, user can turn off the corresponding
function via other equipment or switchover mode.
Read/Write Read
Type of data point 2 byte
Object# 19
Name Outdoor ambient Temperature – Status
Function Feed back the outdoor temperature
Description
Transmission value = actual value, actual value:
16.0~30.0
Read/Write Read
Type of data point 2 byte