S2S KNX Gateway
26
Object# 20
Name Indoor ambient Temperature – Status
Function Feed back the indoor temperature
Description
Transmission value = actual value, actual value:
16.0~30.0
Read/Write Read
Type of data point 2 byte
Object# 21
Name Error Code – Status
Function Feed back error of unit
Description
The lower 8 bit and higher 8 bit are two ASCII code
respectively, 0 refers to no error code.
Read/Write Read
Type of data point 2 byte
Object# 22
Name Project No. of starting indoor uint of gateway – Status
Function
Feed back the engineering number of the current
connected IDU
Description
Transmission value = actual value, actual value:
1~255
Read/Write Read
Type of data point 1 byte