EasyManua.ls Logo

Gree NRQD16G/A-S - Revision of Floor Heating Capacity

Gree NRQD16G/A-S
391 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GMV5 Home DC Inverter Multi VRF Units
31
7.5 Revision of floor heating capacity
Outdoor unit: GMV-S120WL/A-S
Outdoor temperature
Water yielding temperature ()
30
35
40
45
DB
WB
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
-9.8
-11
9.2
2.94
7.7
2.45
6.1
2.47
7.1
2.89
-9.5
-10
9.5
2.97
8.0
2.48
6.5
2.50
7.0
2.86
-8.5
-9.1
9.9
3.01
8.2
2.50
6.9
2.53
6.9
2.83
-5
-5.6
10.8
3.10
9.0
2.59
8.0
2.62
6.8
2.72
-3
-3.7
10.4
3.07
8.7
2.56
7.9
2.62
7.1
2.78
0
-0.7
9.9
3.02
8.3
2.52
7.7
2.61
7.5
2.87
3
2.2
11.9
3.15
9.9
2.63
9.6
2.92
9.1
3.04
5
4.1
13.2
3.24
11.0
2.70
10.8
3.13
10.2
3.16
7
6
14.5
3.33
12.1
2.77
12.0
3.34
11.3
3.27
9
7.9
14.6
3.39
13.5
2.83
12.8
3.16
12.3
3.32
15
13.7
14.6
3.42
14.6
2.87
14.6
3.17
14.6
3.44
Outdoor unit: GMV-S140WL/A-S
Outdoor temperature
Water yielding temperature ()
30
35
40
45
DB
WB
Capacity
Power
Capacity
Power
Capacity
Power
Capacity
Power
-9.8
-11
10.8
3.52
9.0
2.94
7.1
2.96
8.2
3.47
-9.5
-10
11.1
3.56
9.3
2.97
7.6
3.00
8.2
3.43