6.2 Wiring AC Output
WARNING
You must install a separate single-phase circuit-breaker or other load
disconnection unit for each inverter in order to ensure that the inverter
can be safely disconnected under load.
NOTE :The inverter has the function of detecting residual current and
protecting the inverter against residual current. If an external RCD breaker
is
mandatory in the country of installation
,you must choose a
Type B
RCD
breaker with the rating residual
current not less than 300mA.
You must install a separate single-phase circuit-breaker or other load disconnection
unit for each inverter in order to ensure that the inverter can be safely disconnected
under load.
We suggest you choice the AC breaker rating current in this table:
MIC 600TL-X 10A/230V
MIC 750TL-X 10A/230V
MIC 1000TL-X 10A/230V
MIC 1500TL-X 10A/230V
MIC 2000TL-X 16A/230V
MIC 2500TL-X 16A/230V
MIC 3000TL-X 16A/230V
MIC 3300TL-X 16A/230V
The AC wiring step: