BAT is in normal operation
No BAT , PV inverter mode
WiFi/ 4G fail,Local WiFi ok
Local WiFi fail,4G/WiFi ok
Arc Fault(with the buzzer on)
The single LED indicates the operational status of inverter.
7.3.2 LED description
The LED combination indicate the operational status of inverter.
7.4 Powering off the system
7.5 Button
7.5.1 Reset button
Send a shutdown command from the APP. for details, see the Operations on the
Shinephone APP.
Turn off the AC switch between the inverter and the power grid.
Turn off the DC switch at the bottom of the inverter.
If a battery connects to the battery port of the inverter, power off the battery.
The system is shutdown.
After the inverter powers off, the remaining electricity and heat may
still cause electric shock and burns. After power-off, wait 5 minutes
before servicing the inverter. Always wear protective gloves when
servicing the inverter.
If the inverter is connected to the battery, ensure that a shutdown
command is sent from the APP. Power off the system after the inverter has
shut down. If no shutdown command is sent from the app, the inverter
will shut down after the power grid is off, the inverter will wait for
meanwhile, then charge the battery by solar power and the inverter enter
off grid mode.
Power off both Grid, PV and Battery totally, can shut down the system.
WARNING
There is a button located inside the wiring box. for this button,there are the The
ffollowing functions are for reset botton:
Press the button for 3-5 seconds
If there is no arc fault, run arc
self-test
Press the button for 3-5 seconds
Gateway reset to factory
status
Press the button for more than 10
seconds
Fig 7.2
41
42