(7) Click button to apply the change.
(8) Repeat to click button to apply the change again for 5 (FIVE) times.
b) Use ShineBus software to change voltage settings
Tools we need to prepare are: RS232-to-USB cable
Laptop (or computer)
ShineBus software.
• Change tripping voltage Vmax setting
Please follow the below steps to change the tripping voltage Vmax setting:
(1) Get ShineBus software from Growatt and install it to your laptop. Then connect inverter
and laptop via RS232-to-USB cable.
(2) Switch on the DC switch to power on inverter, and switch OFF the AC switch to
disconnect inverter grid connection.
(3) Run ShineBus software.
(4) Choose the option “Parameter”, as follows:
(5) Choose “14. R1 Vac High”, as follows: