20
11
Maximum utility
charging current
12KW model: default 30A, 10A~100A Settable
10KW model: default 30A, 10A~80A Settable
8KW model: default 30A, 10A~70A Settable
6KW model: default 30A, 10A~60A Settable
5KW model: default 30A, 10A~50A Settable
4KW model: default 30A, 10A~40A Settable
(If Li is selected in program 5, this program cant be set up)
12
Setting voltage point
back to utility source
when selecting “SBU
priority” or “Solar
first” in program 01
48V model: default 46.0V, 44.0V~51.2V settable
48V model Lithium mode: default 40%, 5%~50% settable
13
Setting voltage point
back to battery mode
when selecting “SBU
priority” or “Solar
first” in program 01
48V model: default 54.0V, 48.0V~58.0V Settable
48V model Lithium mode: default 80%, 60%~100% settable
14
Charger source priority:
To configure charger
source priority
If this off grid solar inverter is working in Line, Standby or
Faultmode, charger source can be programmed as below:
Solar first
Solar energy will charge battery
as first priority.
Utility will charge battery only
when
solar energy is not available.
Utility first
Utility will charge battery as
first priority.
Solar energy will charge battery
only
when utility power is not
available.
Solar and Utility (Default)
Solar energy and utility will both
charge battery.
Only Solar
Solar energy will be the only
charger
source no matter utility is
available or not.
If this off grid solar inverter is working in Battery mode or Power
saving mode, only solar energy can charge battery. Solar energy
will charge battery if it's available and sufficient.