7.3.2 Startup
If an outlet valve is installed, we recommend that you open the
valve 1/4 of a turn when starting the pump or the system.
Do not operate pumps against a closed valve.
To start up a BMS hp pump, proceed as follows:
1. Start the feed pump (1), and check that the inlet pressure (2) of
the BMS hp pump (6) is higher than 0.5 bar (6" BMS hp) or 1.0
bar (8" BMS hp).
2. Vent the pump.
3. Start the pump.
4. Ramp up the pump according to factory settings. See the figure
below (1).
Ramp up from 0 to 1700 rpm within three seconds.
2
3
1
4
rpm
1700
3s
t[s]
TM061079
Ramping up, BMS hp
Ramp-up time:
Ramp-up: from 0 to 1700 rpm, maximum 3 seconds.
Ramp-up: from 1700 rpm to maximum speed, to be
configured by the customer.
Ramp-down: from maximum speed to 1700 rpm, to be
configured by the customer.
Ramp-down: from 1700 to 0 rpm, maximum 3 seconds.
5. Set the outlet pressure of the pump to the desired value.
6. Check that the inlet pressure of the pump is higher than 0.5 bar
(6" BMS hp) or 1.0 bar (8" BMS hp) and lower than 82.7 bar.
Make sure that the BMS hp pump is protected against dry-
running.
Related information
7.3.1 Before startup
7.3.3
Operating limits
We recommend that you always keep the capacity of the booster
systems within the recommended flow rate and pressure range of
each individual pump.
Note that if there is a risk of exceeding the maximum inlet or outlet
pressure, we recommend that you install a safety valve.
BMS hp
Recommended flow rate at 25 °C (77 °F)
Type
[m
3
/h]
US [gpm]
BMS hp 18-3, 18-5, 18-7 10-26 44 - 114.5
BMS hp 30-3, 30-5, 30-7 19-45 83.7 - 198
BMS hp 46-2, 46-4, 46-6A 28-72 123-317
BMS hp 60-2, 60-4, 60-6 37-90 163 - 396.3
BMS hp 77-2, 77-3 47-120 207-528
BMS hp 95-3 57-143 251-629
BMS hp 125-2 75-187 330-823
BMS hp 160-2 90-215 396-946
BMS hp 215-1 115-310 506-1364
Recommended pressure
Type
Inlet pressure
Outlet
pressure
Min.
[bar]
Min.
[psi]
Max.
[bar]
Max.
[psi]
Max.
[bar]
Max.
[psi]
BMS hp 18-3,
18-5, 18-7
1 14.5 80 1160 82.7 1200
BMS hp 30-3,
30-5, 30-7
1 14.5 80 1160 82.7 1200
BMS hp 46-2,
46-4, 46-6A
1 14.5 80 1160 82.7 1200
BMS hp 60-2,
60-4, 60-6
1 14.5 80 1160 82.7 1200
BMS hp 77-3 1 14.5 80 1160 82.7 1200
BMS hp 95-3 1 14.5 80 1160 82.7 1200
BMS hp 125-2 1 14.5 80 1160 82.7 1200
BMS hp 160-2AA 1 14.5 80 1160 82.7 1200
BMS hp 215-1 1 14.5 80 1160 82.7 1200
Note that higher pressure is available on request.