EasyManua.ls Logo

Grundfos BoosterpaQ PFU 2000 - PMU 2000 Fault Indication Menu; PMU Alarm Examples

Grundfos BoosterpaQ PFU 2000
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PMU fault indication menu
Press the button on the PMU to see the following faults.
The PMU will keep the last 10 faults in memory.
PMU alarm examples
Alarm type: Zone, Pump,
PFU, System.
Time alarm occurred (hh-mm)
24-hour clock.
Detail of alarm: See chart
below.
Time & date alarm cleared. If
“Actual” then alarm still exists.
Date alarm occurred (dd-mm)
Alarm zone A min. limit
10:12 03-11 10:22 03-11
12
PMU alarm display Condition Possible remedy
Alarm System mains drop
10:12 03-11 11:43 29-10
There was a power failure to the system. This is normal during shipping as there was
a power failure to the system. Simply reset
the alarm.
Alarm Zone A max. limit
10:12 03-11 Actual
High System Pressure on discharge.
Possible VFD failure or max. limit set too low.
Solve VFD problem. Adjust max. limit to higher
value (may be too close to set-point (system
pressure).
Alarm Zone A min. limit
10:12 03-11 Actual
Low System Pressure on discharge. Possible
pipe breakage in system or pipes are not yet
filled.
Repair piping. Adjust Min. Limit to a lower
value as it may be set too high (too close to
system pressure).
Alarm Zone A Watershort
10:12 03-11 Actual
Low Suction Pressure. Check suction condi-
tions.
If inlet is pressurized, lower min. pre-pressure. If
flooded suction or suction lift, ensure water is in
suction piping.
Alarm Zone A speed cont.
10:12 03-11 10:16 03-11
Speed Control (Variable Frequency Drive)
Fault.
Check VFD fault log.
Alarm Zone A sensor AI1
10:12 03-11 Actual
Sensor fault on Analog Input 1 (discharge
pressure transducer)
Check transducer connections (may just be
loose wire). Check transducer. Replace if
necessary.
Alarm Zone A sensor AI2
10:12 03-11 Actual
Sensor fault on Analog Input 2 (normally suc-
tion pressure transducer).
Check transducer connections (may just be
loose wire). Check transducer. Replace if
necessary.
Alarm Zone A sensor AI3
10:12 03-11 Actual
Sensor fault on Analog Input 3 (normally
external set-point).
Check external set-point source. Check con-
nection (may be loose or not connected at
all).
Alarm pump: 1 fault
10:12 03-11 Actual
Fault on pump number 1. If pump is on/off pump (constant speed),
check manual motor protector (breaker). If
pump is MLE or Baldor Smartmotor, check
motor fault log or consult motor Installation
& Operating Instructions. Check voltage moni-
tor relay.
Alarm PFU 123
15:12 03-11 Actual
There is a communication error between
the PMU and the PFU that is connected to
pumps 1, 2 and 3.
Check BUS (RS485) connection between PMU
and
PFU. Check power supply to PFU and/
or PMU. Check fuse in PFU.
BpaQ IO INDD.indd 1/28/2005, 11:01 AM12

Related product manuals