Danfoss VLT 8000 Factory Settings (continued)
Extended Menu Programming
Factory Setting Field Changes
Item Number Parameter Value Value # New Value Date
Level 0 007 Large Readout 3
008 Small Display Readout 16
009 Small Display Readout 5
010 Small Display Readout 6
Level 1 101 Torque Characteristics VT Low 2
112 Motor Preheater Disable 0
117 Motor Thermal Protection ETR Trip 1 4
Level 2 208 Automatic ramp-down Disable 0
210 Reference Type External/Preset 2
211 Preset Reference 1 100%
Level 3 302 Pin 18 Start 1
303 Pin 19 Reverse and Start 2
305 Pin 29 Preset Ref. On 6
308 Pin 53 Reference 1
309 Term. 53, Min. Scaling 0.0V
310 Term. 53, Max. Scaling 10V
325 Relay 01, Off Delay 2 sec
Level 4 400 Reset Function Automatic Reset x 10 6
401 Automatic Restart time 5 sec
407 Switching Frequency 4500
408 Interference Reduction Method Fixed Switching Freq. 0
Level 0 016 Lock for data change Locked 1
20
BpaQ IO INDD.indd 1/28/2005, 11:01 AM20