Operating and inlet pressures
CR, CRN 95-155
3
11
3. Operating and inlet pressures
Max. operating pressure and liquid temperature
* For operating pressures above 435 psi (30 bar) the liquid temperature limits are -40 to 176 °F (-40 to 80 °C).
ANSI, PJE (Victaulic type)
Pump type
TM06 9402 2417
Pressure class
Maximum permissible operating
pressure in standard configuration
[psi (bar)]
Liquid temperature
[°F (°C)]
CR 95-1-1 → 95-4-1 150
363 (25)
Note: CRN models may be
configured for up to
580 psi (40 bar)
(depending on model).
Please contact Grundfos.
-22 to 248 (-30 to 120)
CR 95-4 → 95-5-1 300
CR 125-1-1 → 125-3 150
CR 125-4-2 300
CR 155-1-1 → 155-3-2 150
CRN 95-1-1 → 95-4-1 150
-40 to 248 (-40 to 120)*
CRN 95-5-2 → 95-5-1 300
CRN 125-1-1 → 125-3 150
CRN 125-4-2 → 125-7-2 300
CRN 155-1-1 → 155-3-2 150
CRN 155-3-1 → 155-5-1 300