English (GB)
23
2. Current 
consumption
TM00 1372 5092
Measure the amps of each 
phase while the pump is 
operating at a constant 
discharge head (if possible, 
at the capacity where the 
motor is most heavily 
loaded). For maximum 
operating current, see 
nameplate.
For the MS6000P, the 
current consumption must be 
measured between the sine 
wave filter and the motor.
On three-phase motors, the difference between the 
current in the phase with the highest consumption 
and that with the lowest consumption must not 
exceed 5 %. Otherwise, or if the current exceeds the 
rated current, the following faults may occur:
• The contacts of the motor-protective circuit 
breaker burn.
– Replace the contacts or the control box for 
single-phase operation.
• There is poor connection in leads, possibly in the 
cable joint.
– See item 3.
• The mains voltage is too low or too high.
– See item 1.
• The motor windings are short-circuited or partly 
disjointed.
– See item 3.
• Damaged pump is causing the motor to be 
overloaded.
– Pull out the pump assembly for overhaul.
• The resistance value of the motor windings 
deviates too much (three-phase operation).
– Move the phases in phase order to a more 
uniform load. If this does not help, see item 3.
Items 3 and 4: Measurement is not necessary when the supply voltage and the current consumption are 
normal.
3. Winding 
resistance
TM00 1373 5092
Disconnect the submersible 
drop cable from the motor-
protective circuit breaker or 
sine wave filter. Measure the 
winding resistance between 
the leads of the drop cable.
Three-phase motors: The deviation between the 
highest and lowest value must not exceed 10 %. If 
the deviation is higher, pull out the pump assembly. 
Measure motor, motor cable and drop cable 
separately, and repair/replace the defective parts.
Note: On single-phase, 3-wire motors, the operating 
winding will assume the lowest resistance value.