Introduction
3
Medium UPM
1
1. Introduction
Medium UPM - EU range
This data booklet applies to the Grundfos Medium UPM pump range.
Applications
In a modern heating, cooling and domestic hot water
supply system there are different circuits in which
Medium UPM pumps in different versions can be
placed. A differentiation must be made between the
heating (or cooling) production and the distribution.
On the production side there are some applications
where pumps are used in primary or internal circuits
e.g. for geothermal or solar thermal brine circuits.
The distribution side is often split into two circuits - a
primary and a secondary circuit - in order to keep the
flow and temperature independent from each other. A
heat exchanger, a hydraulic separator or a buffer tank
can be used for this separation.
For some heating generators (e.g. condensing boilers,
heat pumps or district heating) it is important to keep
the return temperature as low as possible. Therefore it
is necessary to keep the right balance between flow in
primary and secondary circuits. Without separator, the
primary pump creates a differential pressure in the
secondary circuits. A generator effect can happen in
the secondary pump, from which Medium UPM pumps
are protected.
The primary pump is mostly integrated into the heating
appliance and controlled via a control signal (e.g.
PWM or BUS) to ensure the optimum operation of the
boiler, for instance.
Type P1 max. Control
R 1 1/2" x 130 mm CED
R 1 1/2" x 180 mm CED
R 2" x 180 mm CED
R 1" x 130 mm CED
R 1 1/2" x 180 mm N
UPMM xx-95
100 W
PWM A
●●●●●
UPMM xx-95 AUTO AUTO
●●●●●
UPML xx-105
140 W
PWM A
●●●●●
UPML xx-105 LIN LIN bus
●●●●●
UPML xx-105 AUTO AUTO
●●●●●
SOLAR PML xx-145 140 W PWM C
●●●●●
UPMXL xx-125
180 W
PWM A
●●●●●
UPMXL xx-125 LIN LIN bus
●●●●●
UPMXL xx-125 AUTO AUTO
●●●●●
UPMXXL xx-120
180 W
PWM A
●●
UPMXXL xx-120 AUTO AUTO
●●
Application Recommended pump type
Heat production or heat
transmission side
Gas or oil-fired space and combination heaters UPMM/UPML/UPMXL/UPMXXL PWM/LIN
Solid fuel heaters UPMM/UPML/UPMXL/UPMXXL AUTO
Heat pumps (brine side) UPMM/UPML/UPMXL/UPMXXL PWM/LIN
Heat pumps (heating side) UPMM/UPML/UPMXL/UPMXXL PWM/LIN
Mini combined heat and power cogeneration UPMM/UPML/UPMXL/UPMXXL PWM/LIN
Thermal solar system (collector side) SOLAR PML
District heating systems with heat exchanger UPMM/UPML/UPMXL/UPMXXL PWM/LIN
Heat distribution side
Space heating systems UPMM/UPML/UPMXL/UPMXXL AUTO
Space heating and cooling systems UPMM/UPML/UPMXL/UPMXXL AUTO
Domestic hot water generation (heating side) UPMM/UPML/UPMXL/UPMXXL PWM/LIN
Domestic hot water generation (DW side) UPMM/UPML/UPMXL AUTO N
Domestic hot water recirculation UPMM/UPML/UPMXL AUTO N