EasyManua.ls Logo

Grundfos UPS3 15-50/65 - Selecting Control Modes; PWM Signal Control

Grundfos UPS3 15-50/65
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
English (GB)
12
6.2.4 Selecting the control modes
Proportional pressure
We recommend proportional-pressure mode in variable flow
systems with relatively large pressure losses in the distribution
pipes such as:
two-pipe heating systems with thermostatic valves and long
distribution pipes
two-pipe heating systems with thermostatic valves and high
pressure losses in system parts with total flow
primary circuit pumps in systems with large pressure losses in
the primary circuit.
Note: Proportional-pressure mode is not recommended in
heating systems that includes an automatic bypass valve to
ensure a minimum flow for the heating appliances.
Constant pressure
We recommend constant-pressure mode in variable flow systems
with relatively small pressure losses in the distribution pipes such
as:
two-pipe heating systems with thermostatic valves and
dimensioned for natural circulation (former gravity systems)
two-pipe heating systems with thermostatic valves and low
pressure losses in system parts with total flow
one-pipe heating systems with thermostatic valves or pipe
balancing valves
underfloor heating systems with zone valves
primary circuit pumps in systems with small pressure losses in
the primary circuit.
Constant curve
We recommend constant-curve mode in constant-flow systems,
where both a constant flow rate and a constant head are required,
such as:
heat surfaces
replacement for uncontrolled circulators, for instance
integrated in boilers.
6.2.5 Externally controlled signal connection: PWM input
signal profile A (heating)
The UPS3 can be controlled via a digital low-voltage pulse-width
modulation (PWM) signal. For instructions on how to set the
connection, see section 7.3 Setting the PWM input signal.
The circulator runs on constant-speed curves depending on the
PWM input signal. The speed decreases when the PWM value
increases. If PWM equals 0, the circulator runs at maximum
speed.
Fig. 16 PWM input signal profile A (heating)
6.2.6 PWM feedback signal - power consumption
The PWM feedback signal offers pump information like in BUS
systems:
current power consumption (accuracy ± 2 % of PWM signal)
warning
•alarm
operation status.
Alarms
Alarm output signals are available because some PWM output
signals are dedicated to alarm information. If a supply voltage is
measured below the specified supply voltage range, the output
signal is set to 75 %. If the rotor is locked due to deposits in the
hydraulics, the output signal is set to 90 % because this alarm
has a higher priority. See fig. 17.
Fig. 17 PWM feedback signal - power consumption
TM06 9136 1617
PWM input signal [%] Pump status
10 Maximum speed: max.
> 10 / 84 Variable speed: min. to max.
> 84 / 91 Minimum speed: IN
> 91/95 Hysteresis area: on/off
> 95 or 100 Standby mode: off
PWM input signal [%]
Max.
Speed
PWM input signal [%]
Max.
Speed [rpm]
TM07 1313 1118
25 50 100 150 200 250
10
20
30
40
50
60
70
80
90
100
Power [W]
Standby (stop)
Alarm stop: fault, blocked pump
Alarm stop: electrical fault
Warning Saturation at 70 Watt
S
l
o
p
e
:
1
W
/
%P
W
M
PWM output signal [%]

Related product manuals