ERROR CODES & PROBLEM SOLVING
PAGE 33
ENGLISH
IPM Protection
Outdoor Display
 
LED1 Flashes 2 Times
 
Under this error, please ensure the refrigerant system 
pressure is normal with no blockages, then replace power 
module
Spare Parts:
Power module
Refrigerant 
Turn the unit on.
Is the error displayed before 
the compressor starts?
The power module is faulty, 
replace the module
Problem persists?
Check for proper 
refrigerant charge
The compressor starts normally, but 
malfunctions are reported after it has 
operated for a period of time.
No
Yes
Yes
Yes
Yes
Over-current of the Compressor
Outdoor Display
 
LED1 Flashes 3 or 24 or 25 Times
 
Spare Parts:
Power module
Refrigerant 
The compressor starts 
normally, but malfunctions are 
reported after it has operated 
for a period of time.
Correct the power supply
Turn the unit on.
Is the error displayed before 
the compressor starts?
Is the power supply 
voltage normal?
Check the refrigerant 
charge
The power module is 
faulty, replace the power 
module
Yes Yes
Yes
No
No