Functions and control
18 Domestic air conditioner
7.1.4 Four way control
For the details of defrosting four-way valve control, see the defrosting process.
Four way working in other ways:
Under the mode of heating, open the four-way valve, when the compressor is not started or
changed to non-heating mode, make sure the compressor is stoped for 2 minutes, and then close the
four-way valve.
7.1.5 Protection function
7.1.5.1 TTC high temperature-preventing protection
Once the machine is started, it can run TTC(air-blowing temp) overheating protection of
air-blowing, but air-blowing sensor malfunction must alarm after 4 minutes during which the
compressor is started (during the course of self-detection, there’s no such limitation)
Sensor detection methods: 100 times (one cycle of procedure run is one time, and about 5ms,
detection method for each time: continuously sampling for 8 times, then order them and take the mean
value of the middle 2 values), take the mean value.
TTC˄ć˅
Abnormal stop
110
Decreasing the frequency rapidly˄1HZ/second˅
100
Decreasing the frequency slowly (1HZ/10seconds)
98
The frequency doesnt change.
93
Increasing the frequency (1HZ/10second)
90
Increasing the frequency˄1HZ/1second˅
TTC>=110ć lasts for 20 seconds. Overheating protection of air-blowing, alarm malfunction to the
indoor, others don’t last.
7.1.5.2 TC high temperature-preventing control of the indoor heating unit˖
Tpg_indoor is the highest value of the effective indoor unit (start it and it is in accord with the
running state). TC=indoor coil temp.
The indoor heat exchanger sensor tests the temperature of the indoor heat exchanger. If the
temperature is higher than 55ć, decrease the rotate speed of the compressor and do the high
temperature-preventing protection of the indoor heat exchanger; if the temperature of the indoor heat
exchanger is lower than 47ć, recover to the normal control.