49-7835   Rev. 8 9
ENGLISH  
Step 1 - Preparation
Select the Outdoor location:
•  Choose a level place solid enough to bear the weight 
and vibration of the OD unit and where the operation 
noise will not be amplified.
•  Choose a location where the hot air discharge and/or 
noise will not create a nuisance for neighbors.
•  Ensure there is sufficient space to maneuver the OD 
unit into place.
•  Ensure there is sufficient space and no obstructions 
for the air inlet and outlet.
• I nstall the unit’s power/communication wiring at 
least 10 feet away from television and radio sets to 
prevent interference.
•  Ensure any moisture sensitive items are kept away 
from the condensate drain path of the OD unit.
NOTES:
•  OD unit cannot hang from a ceiling or be stacked.
•  Ensure that accumulated snow and debris will not 
block the air inlet or the coil if installing the outdoor 
unit with a fence or guard rail around it.
•  Ensure ventilation in case of refrigerant leakage.  
R-410A is a safe, nontoxic, and nonflammable 
refrigerant.
•  Avoid installing the OD unit where corrosive gases, 
such as sulfur oxides, ammonia, and sulfurous gas 
are produced.  Consult with an installation specialist 
about using a corrosion-proof or anti-rust additive to 
protect the unit coils.
≥
6(150)
≥
20(500)
≥
8(200)
≥
6(150)
≥
12(300)
≥ 6(150)
≥
40(1000)
INSTALLATION INSTRUCTIONS