Installation Procedure
16
Electrical Wiring
Selection of size of power supply and interconnecting wires
Precautions for Electrical wiring
Electrical wiring work should be conducted only by authorized personnel.
Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated
grip on the ends of the wires.
Use copper conductor only.
Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage
drop.)
DANGER OF BODILY INJURY OR DEATH
TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC
CONNECTIONS.
GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.
WARNING!
Item
Model
Phase
Switch breaker
(A)
Circuit breaker
Overcurrent protector
rated capacity (A)
Power source
wire size
(minimum)
(mm
2
)
Switch
breaker(A)
Earth leakage breaker
Leak
current(mA)
1U28HS1ERA
1U36HS1ERA
1U48LS1ERA
1U60IS1ERA
301 40 30 6.0 40
3 30 4.0 3020 30
1U48LS1ERB
1U60IS1ERB
AU60NAIESA
1U48LS1EAB
1U48IS1EAB
1U60IS1EAB
3 30 4.0 3020 30
If the supply cord is damaged, it must be replaced by the manufacturer or itsservice agent or a similar qualified person.
If the fuse of control box is broken, please change it with the type of T25A/450VAC;
If the fuse of control PC board is broken, please change it with the type of T3.15A/250VAC. But for 1U28HS1ERA,
1U36HS1ERA,1U48LS1ERA,,1U48LS1ERB,1U60IS1ERA,1U60IS1ERB, AU60NAIESA, the type is T6.3A/250VAC.
The wiring method should be in line with the local wiring standard.
The power cable and connecting cable should be self-provided.
All the cables shall have got the European authentication certificate. During installation, when the connecting cables
break off, it must be assured that the grouding wire is the last one to be broken off.
The breaker of the air conditioner should be all-pole switch; and the distance between its two contacts should not be no
less than 3mm. Such means for disconnection must be incorporation in the fixed wiring.
The distance between its two terminal blocks of indoor unit and outdoor unit should not be over 5m. If exceeded, the
diameter of the wire should be enlarged according to the local wiring standard.
A leakage breaker must be installed.
The specification of power cable
For models 1U28HS1ERA, 1U36HS1ERA,
1U48LS1ERA,1U60IS1ERA
the power cable should be H05RN-F 3G 6.0mm
2
.
For models 1U48LS1EAB,
1U48IS1EAB,
1U60IS1EAB, 1U48LS1ERB, 1U60IS1ERB, AU60NAIESA, the power cable
should be H07RN-F 5G 4.0mm
2
.