2HUM18HC03/R2(DB)-SM  Wiring diagrams 
62
Domestic air conditioner
7.3.11 
Loss of synchronism detection 
Inverter side current detection is abnormal 
Outdoor Display
LED1  flash 18 times  
     LED1  flash 19 times 
Method of   
  The position of the compressor rotor can not detected normally
Malfunction 
Detection 
Malfunction    
    when the wiring of compressor is wrong or the connection is poor;
Decision       
 or the compressor  is damaged 
Conditions 
 
Supposed         Ŷ
Faulty  The wiring of compressor 
Causes  Ŷ
 Faulty  compressor
Faulty  PCB 
 
Troubleshooting    
* Caution   
Be sure to turn off power switch before connect or disconnect connector, or 
parts damage may be occurred. 
Within 3 minutes after the machine is
supplied with power and turned on with
the remote controller,check whethe
the compressor can    stard up 
1. The wiring of compressor is incorrect 
or the connection is poor; 
2. The compressor is damaged 
At frist, the compressor start up ,soon the 
compressor stopped with the LED1 on the 
outdoor PCB blinks˄1Hz˅19/18 times 
IPM Module is damaged and needs 
replacing.
the Malfunctions exist also, the 
compressor is damaged replace a 
new one 
YES 
NO
YES 
Malfunction unsolved 
Maybe there is some disturbance