174
Communication wiring
Communication wiring length (m/
ft)
Dimensions of wiring
< 100m/328ft
0.3mm
2
x3-core shielded
wire (22AWG,3wire)
≥100m/328ft and <200m/656ft
0.5mm
2
x3-core shielded
wire (20AWG,3wire)
≥200m/656ft and <300m/984ft
0.75mm
2
x3-core shielded
wire (18AWG,3wire)
≥300m/984ft and <400m/1312ft
1.25mm
2
x3-core shielded
wire (16AWG,3wire)
≥400m/1312ft and <500m/1640ft
2mm
2
x3-core shielded wire
(14AWG,3wire)
1. First, put communication wire through the hole in the back
cover.
Wired Controller Wiring Instruction
Press this button to open the back
cover of the wired controller.
2. Fix back cover to the holder. After that, connect
communication wire to CON1 port of wired controller. Finally
put the front cover of wired controller to back cover to complete
the installation.
C
C
A
CON1
B
3
2
1
B
red
yellow
white
A