EasyManua.ls Logo

Haier AD140S2SM3FA - Page 111

Haier AD140S2SM3FA
257 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
108
Item Model
3U55S2SR2FA
Piping
Refrigerant
Type / Charge kg R32 / 1.6
GWP 675
No Need to Recharge m 30
Recharge g/m 20
Pipe
Liquid mm 3*Φ6.35
Gas mm 3*Φ9.52
Connecting Method - Flared
Between
I.D &O.D
Drop Between IU & OU m ≤7.5
Piping Length Between IU & OU m ≤10
Total Liquid Piping Length m ≤30
Drop Between Indoor Units m ≤1
Max. Drop Between IU &OU m 15
Max. Drop Between Indoor Units m 7.5
Max. Piping Length Between IU & OU m 25
Max. Cable Length Between IU & OU m 30
Max. Total Length m 50
Working Temperature
Cooling °C -10~46
Heating °C -15~24
Tdisignh: -10°C Tbivalent: -7°C TOL: -15°C
Pto: 30W Psb: 13W Pck: 0W Poff: 0W
Cooling
A (Cap/EER) 5594W/3.81
Heating
A (Cap/COP) 3956W/2.62 Tol (Cap/COP) 4553W/2.67
B (Cap/EER) 3890W/6.44 B (Cap/COP) 2746W/4.05 Tb (Cap/COP) 3956W/2.62
C (Cap/EER) 2465W/10.31 C (Cap/COP) 1546W/4.60 Cd (cooling) 0.25
D (Cap/EER) 2680W/14.73 D (Cap/COP) 1386W/5.75 Cd (heating) 0.25
Max.Cooling Condition
Indoor Temperature:
32°C/23°C
Max. Heating Condition
Indoor Temperature: 27°C/-°C
Outdoor Temperature:
46°C/-°C
Outdoor Temperature: 24°C/18°C
kWh/Annum 258 kWh/Annum-Average 1679
kWh/Annum-
Warm
801
1. The above performance data are from the combination of 3U55S2SR2FA+3*AS25S2SF2FA.
2. Large drop and long piping installation will obviously reduce the total capacity.

Other manuals for Haier AD140S2SM3FA

Related product manuals