109
Item Model
3U70S2SR2FA
Function - Cooling Heating
Rating Capacity W 7000 7600
Cooling Pdesign W 7000
Heating Pdesign (-10°C) W 6000
Rated Power Input (Indoor + Outdoor) W 1750 1800
Rated Current Input (Indoor + Outdoor) A 8.3 8.3
EER/COP W/W 4.0 4.2
SEER/SCOP W/W 7.5 4.2
Minimum Capacity W 2400 2900
Minimum Power Input W 550 550
Maximum Capacity W 7600 8500
Maximum Power Input (Indoor + Outdoor) W 2700 2300
Power Source - 1PH, 220-240V~, 50/60Hz
Max. Running Current (Indoor + Outdoor) A / A 11.9 9.7
Power Facor (Under Rating Power Input) - 99% 99%
Starting Current A 4
Fuse Size (Recommended Size) A 25
Outdoor Unit
Compressor
Model/Manufacture - SVB140FCAMC-L/ MELCOM
Oil Charge and Type - 500CC/ FW68S
Type - Twin Rotary (DC Inverter)
Number - 1
Fan
Type × Number - Axial × 1
Speed r/min High 700
Motor Output/Input Power W 90/130
Air-Flows (H/M/L) m³/h About 3000
Heat Exchanger
Type/Diameter mm TP2M / 7.0
Row - 2
Face Area About 0.6
Dimension
(WxDxH)
External mm 890/340/700
Package mm 998/443/770
Refrigerant Control Method - EEV
Defrosting Method - Automatic by Reversible Cycle
Crankcase Heater Power W None
Noise Level
Sound Power Level dB(A) 66
Sound Pressure Level dB(A) 53
Weight Net/Shipping kg / kg 54/58