110
Item Model
3U70S2SR2FA
Piping
Refrigerant
Type/Charge kg R32 / 1.6
GWP 675
No Need to Recharge m 30
Recharge g/m 20
Pipe
Liquid mm 3* Φ6.35
Gas mm 3* Φ9.52
Connecting Method - Flared
Between
I.D &O.D
Drop Between IU & OU m ≤7.5
Piping Length Between IU & OU m ≤10
Total Liquid Piping Length m ≤30
Drop Between Indoor Units m ≤1
Max. Drop Between IU &OU m 15
Max. Drop Between Indoor Units m 7.5
Max. Piping Length Between IU & OU m 25
Max. Cable Length Between IU & OU m 30
Max. Total Length m 60
Working Temperature
Cooling °C -10~46
Heating °C -15~24
Tdisignh: -10°C Tbivalent: -7°C TOL: -15°C
Pto: 30W Psb: 13W Pck: 0W Poff: 0W
Cooling
A (Cap/EER) 7128W/3.83
Heating
A (Cap/COP) 4755W/2.92 Tol (Cap/COP) 5518W/2.62
B (Cap/EER) 5065W/5.82 B (Cap/COP) 3221W/4.01 Tb (Cap/COP) 4755W/2.92
C (Cap/EER) 3362W/9.72 C (Cap/COP) 2080W/5.42 Cd (Cooling) 0.25
D (Cap/EER) 2706W/14.87 D (Cap/COP) 1602W/6.46 Cd (Heating) 0.25
Max. Cooling Condition
Indoor
Temperature:
32°C/23°C
Max. Heating Condition
Indoor Temperature: 27°C/-°C
Outdoor
Temperature:
46°C/-°C
Outdoor Temperature: 24°C/18°C
kWh/Annum 332 kWh/Annum-Average 2012 kWh/Annum-Warm 845
1. The above performance data are from the combination of 3U70S2SR2FA+3*AS25S2SF2FA.
2. Large drop and long piping installation will obviously reduce the total capacity.