216
2. Pipe “b” diameter (between manifold pipes)
Note: Adjust the diameter on job site (changing pipe is needed)
When the latter indoor total capacity is less than 14.0kw, pipe b will use the specication as the pipe a.
3. Pipe “c” diameter (main pipe, between outdoor branch pipe and the rst manifold pipe)
Note: When the distance from outdoor to the farthest indoor is over 80m, the enlarged diameter should be chosen
for the main pipe.
Total indoor capacity after the manifold pipe (kW)
<16.8kW 15.88
19.05
22.22
28.58
28.58
31.8
38.1
9.52
9.52
9.52
12.7
15.88
19.05
19.05
Gas pipe (mm) Liquid pipe (mm)
16.8KW≤X<22.4kW
22.4KW≤X<33.0kW
33.0KW≤X<47.0kW
47.0KW≤X<71.0kW
71.0KW≤X<101.0kW
≥101.0kW
Outdoor capacity
Main pipe Enlarged main pipe
Gas pipe (mm) Liquid pipe (mm) Gas pipe (mm) Liquid pipe (mm)
23.5kW Ø19.05 Ø9.52 Ø22.2 Ø12.7
29.3kW Ø22.2 Ø9.52 Ø25.4 Ø12.7
35.1kW Ø25.4 Ø12.7 Ø28.58 Ø12.7
47.0kW Ø28.58 Ø15.88 Ø31.8 Ø15.88
52.8kW Ø28.58 Ø15.88 Ø31.8 Ø15.88
58.6kW Ø28.58 Ø15.88 Ø31.8 Ø15.88
64.4kW Ø28.58 Ø15.88 Ø31.8 Ø15.88
70.2kW Ø31.8 Ø19.05 Ø38.1 Ø19.05
76.3kW Ø31.8 Ø19.05 Ø38.1 Ø19.05
82.1kW Ø31.8 Ø19.05 Ø38.1 Ø19.05
87.9kW Ø31.8 Ø19.05 Ø38.1 Ø19.05
93.7kW Ø31.8 Ø19.05 Ø38.1 Ø19.05
99.5kW Ø31.8 Ø19.05 Ø38.1 Ø19.05
105.3kW Ø38.1 Ø19.05 Ø38.1 Ø22.22