229
Power wiring gure
Please make sure that when the unit is running, the input voltage is no less than 380V;
if it is lower than 380V, the unit may run abnormal.
Indoor and outdoor use their individual power source.
All indoors use one power source.
Install the leakage breaker and the over current breaker, or electric shock will occur.
Outdoor power source and power cable
Power cable must be xed rmly.
Each outdoor must be earthed well.
When power cable exceeds the range, thicken it appropriately.
Item
Model
Power
source
Power
cable
section
(mm
2
)
Wire
length
(m)
Circuit
breaker
(A)
Rated current of residual
circuit breaker (A)
Ground fault interrupter (mA)
response time (S)
Ground wire
Section
(mm
2
)
Screw
Individual power
AV08IMWEWA
3N~,
380-
400V,
50/60 Hz
6 60 40 40A 30mA below 0.1S 3.5 M5
AV10IMWEWA 10 60 40 40A 30mA below 0.1S 3.5 M5
AV12IMWEWA 10 60 50 50A 30mA below 0.1S 3.5 M5
Power source: 1PH, 220-230V~, 50/60Hz
Power source: 1PH, 220-230V~, 50/60Hz
Power source: 1PH, 220-230V~, 50/60Hz
Leakage breaker
Leakage breaker Leakage breaker Leakage breaker
Leakage breaker Leakage breaker
Over current breaker
Over current breaker Over current breaker Over current breaker
Over current breaker Over current breaker
Outdoor 1
Indoor 1 Indoor 2 Indoor 3
Outdoor 2 Outdoor 3
Power source: 3N~, 380-400V, 50/60Hz Power source: 3N~, 380-400V, 50/60Hz Power source: 3N~, 380-400V, 50/60Hz