Indoor power source and communication wiring
Power cable and communication wire must be xed rmly.
Each indoor must be grounded well.
When power cable exceeds the range, increase the gauge appropriately.
Shielded layer of communication wires must be connected together and be earthed at single point.
The total length of communication wire cannot exceed 1000m.
Shielded layer of communication wire must be grounded at one end.
The total length cannot exceed 600m.
Communication wire for wired controller
Indoor
total
current (A)
Power
cable
section
(mm
2
)
Rated
current of
overcurrent
breaker
(A)
Rated current of residual
circuit breaker (A)
Ground fault interrupter
(mA)
response time (S)
Wire
length
(m)
Outdoor/indoor
(mm
2
)
Indoor/indoor
(mm
2
)
Communication wire section
20A, 30mA, below 0.1s
30A, 30mA, below 0.1s
40A, 30mA, below 0.1s
50A, 30mA, below 0.1s
2-core × (0.75-2.0mm
2
)
shielded wire
≥10 and <15
≥15 and <22
≥22 and <27
Item
<10
3.5
5.5
10
23 20
30
40
50
24
27
42
2
Wire length(m)
<100
≥100 and <200
0.3mm
2
×(3-core) shielded wire 1.25mm
2
×(3-core) shielded wire
2mm
2
×(3-core) shielded wire
0.5mm
2
×(3-core) shielded wire
0.75mm
2
×(3-core) shielded wire
≥200 and <300
≥300 and <400
≥400 and <600
Wire length(m)
Wire spec
Wire spec