193
• Before Starting the Test Running, Please Conrm the Following Works Have been Done Successfully.
1) Correct piping work
2) Correct wiring work
3) Correct match of indoor and outdoor unit
4) Proper recharge of refrigerant if needed.
• Make sure that all the stop valves are fully open.
• Check the voltage supplied to the outdoor and indoor units, please conrm that is 220-240v. 
• Wiring error check
This product is capable of automatic checking of wiring error.
Switch on all the 4 dip-switches on the outdoor unit small service PC-board as shown on the right. 
Then power off the unit and power on again the system will enter the operation of "Wiring Error 
Check". After 
3 Minutes stand-by the unit starts for automatic wiring checking.
Approximately 30~50minutes (depends on how many units installed in the system) after the unit 
starts the Errors of the wiring will be shown by the LEDs (1 to 3).
During this operation, the digital-number will alternately show the compressor working frequency (e.g. 50 stands for 
the current running frequency) and letter "CH"(means checking).
After this operation, if all the wiring is correct, the digital-number will show "0", if there has wrong wiring, the digital-
number will show "EC"(error connection) and also it will ashing.
The service monitor LEDs indicate the error of wiring, as shown in the table below. For details about how to read 
the LED display, refer to the service manual.
If self-checking is not possible, check the indoor unit wiring and piping in the usual manner.
• Test running.
1) To test cooling, set the lowest temperature at 16°C. To test heating, set the highest temperature, at 30°C. 
If the temperature is lower than 16°C, it is impossible to test cooling with remote controller, and also when the 
temperature is higher than 30°C, it is impossible to test heating.
2) Please check both cooling and heating operation of each unit individually and then also check the simultaneous 
operation of all indoor units.
3) After running the unit for about 20 minutes, check the indoor unit outlet temperature.
4) After the unit is stopped, or working mode changed, the system will not start again for about 3 minutes.
5) During cooling operation, frost may occur on the indoor unit or pipes, this is normal.
6) Operate the unit according to the operation manual. Please kindly explain to our customers how to operate 
through the instruction manual.
• Seven-segment Numeric Display
1) When unit is running, this seven-segment numeric will display the frequency of compressor. For 
example, "        " means compressor running frequency is 40 Hz, "      " means compressor running 
frequency is 108Hz.
2) When faulty happens, seven-segment numeric will ash and display some numbers, this number 
is failure code. For example, a ashing "       " means No.15 failure, that is indoor and outdoor 
communication error.
Test Running
LED 1 2 3 4 5 Message
Status
OFF Unit Not Connected
ALL Flashing
Automatic Checking Impossible, All Units 
Connect Wrong
ALL ON All Units Connect Correctly
ON FLASHING FLASHING ON FLASHING
On: Unit Connect Correctly
Flashing: Unit Connect Wrong, Need To 
Change The Wiring Manually Between 2,3, And 
5
ON FLASHING FLASHING ON ON
On: Unit Connect Correctly
Flashing: Unit Connect Wrong, Need To 
Change The Wiring Manually Between 2,3
Only One LED Flashing Abnormal