42
Item Model AD71S2SS1FA
Function —— Cooling Heating
Capacity W 7100 7500
Sensible Heat Ratio W 0.71 /
Dehumidifying Capacity 10-³xm³/h 1.0
Indoor Unit
Power Supply 1PH, 220-240V~, 50/60Hz
Fan
Type × Number —— Centrifugal*3
Speed (H-M-L) r/min 1250/1100/1000/900
Fan Motor Output/lnput Power W 48/55
Air-Flows (H-M-L) m³/h 1000/850/750/650
External Static Pressure pa 0/10/20/30
Heat Exchanger
Type / Diameter mm Inner Grooved Pipe/
7.0
Row —— 3
Total Area 0.11
Temp.Scope °C 2.0-7.0
Dimension
(LxWxH)
External mmxmmxmm 1170x420x185
Package mmxmmxmm 1365x540x270
Drainage Pipe (Material,I.D/O.D) mm PVC 25/29
Control Type (Remote/Wired)
Wired YR-E17(O) or
Remote YR-HBS01(O)
Fresh Air Hole Dimension mm None
Electricity Heater kW None
Noise level
(H-M-L)
Sound Power Level dB(A) 57
Sound Pressure Level dB(A) 38/35/33/30
Weight (Net/Shipping) kg/kg 24/30
Panel
(Optional)
Panel Model (Color) P1B-1210IA/D
Dimension
External (L-W-H) mmxmmxmm
1210/190/100 (Outlet Panel)/
1210/290.5/32.4 (Inlet Panel)
Package (L-W-H) mmxmmxmm 1258/335/220
Weight (Net/Shipping) kg/kg 5/6
Piping
Refrigerant Type R32
Pipe
Liquid mm Φ9.52(3/8)
Gas mm Φ15.88(5/8)
Connecting Method Flared
Norminal condition: indoor temperature (Cooling): 27°C DB/19°C WB, indoor temperature (Heating): 20°C DB
Outdoor temperature (Cooling): 35°C DB/24°C WB, outdoor temperature (Heating): 7°C DB/6°C WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated
sound intensity meter.