Functions and control
15                                      Domestic air conditioner 
7.1.3      Dehumidifying mode. 
* temperature control range: 16---30
* temperature difference:      1
Control feature: send the dehumidifying signal to the outdoor system. 
When Tr>Ts+2
, the compressor will be turned on, the indoor fan will operate at the set speed. 
When Tr  is between  the  Ts and Ts+2
, the  outdoor system  will operate  at the  high dehumidifying   
frequency for 10 minutes and then at the low dehumidifying    mode for six minutes. The indoor fan will 
operate at low speed. 
When Tr< Ts-1.5
, the outsystem will be stopped, the indoor fan will be stopped for 3 minutes and 
then turned to the low speed option. 
All the frequency converses have a 
1   difference. 
    * Wind speed control: Automatic:   
When Tr
 Ts+ 5 , high speed. 
When Ts+3
Tr< Ts+5 , medium speed. 
When Ts+2
Tr< Ts+3 , low speed. 
When Tr<Ts+2
, light speed. 
If the outdoor fan stopped, the indoor fan will be paused for 3 minutes. 
If the outdoor fan stopped for more than 3 minutes and the outdoor system still operates, the system 
will be changed into light speed mode. 
When the airflow speed has no delay from the high to low switching, the speed should be delayed for 
3 minutes (remain at high speed for 3 minutes.) before the next switch. 
Manual: When the  sensor is  off or  Tr< Ts+3
, the manual  operation can not be made.  (obligatory 
automatic operation.) 
*Airgate location control: the location for the airgate can be set according to your needs. 
*Defrosting  function:  preventing  the  frosting  on  the  indoor  heat  exchanger  (when  cooling  or 
dehumidifying). When the compressor works continuously for 6 minutes and the temperature of the 
indoor coils has been below 1
  for 10 seconds, the compressor will be stopped and the malfunction 
will be recorded in the malfunction list. The indoor system will continue to run. When the temperature 
of the indoor coil is raised to 9
, the compressor will be restarted again (the requirement of 3 minutes’ 
delay should be satisfied.) 
*  Coil  protection  (synchronic  overheating  protection)  are  installed  for  the  four  directions  latch 
sectioon 1
(COOL)
sectioon 2(DRY)
sectioon 3(STOP)