Functions and control
19                   Domestic air conditioner 
7.1.11 Low load protection control 
In order to prevent the frosting of the indoor heat interaction device, the outdoor system will be 
stopped if the indoor heat interaction temperature is below 1ć  centigrade for 5 minutes, but the fan 
will continue to operate. The outdoor system will be started again when the heat interaction 
temperature is above 9 centigrade and the system has been stopped for 3 minutes. The malfunction 
will be stored in the malfunction resume and will not be revealed 
7.1.12 High load protection control 
The outdoor system will be stopped if the coil temperature is above 63ć  for 2 minutes. The indoor 
fan will be controlled by the thermostat. The outdoor system can be restarted when the coil 
temperature is below 45ć  and the system has been stopped for 3 minutes. The malfunction will be 
stored in the malfunction resume and will not be revealed. 
7.1.13 Abnormal operation of indoor system
When the outdoor system operates, if the indoor system operation differs from the outdoor system, 
the abnormal operation malfunction will be reported. 10s after the report, the indoor system will be 
closed. 
Outdoor system mode     Indoor system mode        conflicts 
cooling       heating     yes 
cooling       cooling     no 
cooling       airflow     no 
heating       heating     no 
heating       airflow     yes 
heating       cooling     yes 
7.1.14 Malfunction list resume. 
Nothing is presented if there is no code list. 
The malfunction display will automatically finish in 10 seconds. 
The remote control only receives the signals for stop. According to the signals, the malfunction 
resume presentation finishes. 
The resume restores after the power supply restores. 
7.1.15 Abnormality confirmation approaches 
1. indoor temperature sensor abnormality:
Under the operation, the normal temperature ranges from 120 degree to -30 degree. When the 
temperature goes beyond this range, the abnormality can be confirmed. If the temperature goes back 
into the range, the system will automatically resume. 
2 .indoor heat interaction sensor abnormality:
Under the operation, the normal temperature ranges from 120 degree to -30 degree. When the 
temperature goes beyond this range, the abnormality can be confirmed. If the temperature goes back 
into the range, the system will automatically resume.