Service Diagnosis
54 
 Domestic Air Conditioner
7.4.4 Outdoor DC fan motor fault 
Check whether Terminal on the outdoor 
mainboard is well inserted.   
Is it normal? 
Yes
NO 
Reinsert the terminals 
Electrify the machine again and turn it 
on in the Cool state with the remote 
controller. check whether motor can 
run˛ 
Yes 
Measure the voltage between 3 and 6 of 
the terminal about 0-5v. 
Is it normal? 
N0 
the motor of the outdoor unit is damaged and 
needs replacing. 
Measure the voltage between 1 and 3 of the terminal of 
fan motor on the mainboard about DC310V,Measure the 
voltage between 3 and 4 of the terminal about DC15V. 
Measure the voltage between 5 and 3 of the terminal 
about 1-6v.   
NO 
Is it normal? 
The mainboard of the outdoor unit is 
damaged and needs replacing 
N0 
Yes 
Yes