Service Diagnosis
58
Domestic Air Conditioner
7.4.8 Power Supply Over or under voltagve fault
outdoor display: LED1 flash 6 times The power supply is over voltage
Method of
An abnormal voltage rise or fall is detected by checking the specified voltage detection circuit.
Malfunction
Detection
Malfunction
An voltage signal is fed from the voltage detection circuit to the microcomputer
Decision
Conditions
Supposed
Supply voltage not as specified
Causes
the IPM module is broken
the outdoor PCB is broken
Troubleshooting
* Caution
Be sure to turn off power switch before connect or disconnect connector, or else
parts damage may be occurred.
Electrify the machine again and turn it on with
the remote controller. Check whether the
compressor is started normall
y
Is it ok?
Yes
Maybe there is some disturbance
NO
No
~230 is ok?
Yes
Yes
This question may be caused by the power.Repair
the power supply.
NO
Change the IPM module
Change the IPM module
Test the outdoor power supply
(+310VDC) with a multimeter.
check whether the power is
>150 V or <390V?

Other manuals for Haier HSU-09HEG03/R2(DB)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Haier HSU-09HEG03/R2(DB) and is the answer not in the manual?

Haier HSU-09HEG03/R2(DB) Specifications

General IconGeneral
BrandHaier
ModelHSU-09HEG03/R2(DB)
CategoryAir Conditioner
LanguageEnglish

Related product manuals