Service diagnosis
Domestic Air Conditioner
6.3.5 IPM protection
Outdoor display: LED1 flash 2 times
Method of
IPM protection is detected by checking the compressor running condition and so on
Malfunction
Detection
Malfunction
The system leads to IPM protection due to over current
Decision
The compressor faulty leads to IPM protection
Conditions
circuit component of IPM is broken and led to IPM protection
Supposed
IPM protection dues to the compressor faulty
Causes
IPM protection dues to faulty PCB of IPM module
■ Compressor wiring disconnected
Troubleshooting
* Caution
Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
Electrify the machine again and turn it on
with the remote controller,If malfunctions
are reported before or upon the compresso
r
being started up,
IPM Module is damaged and
needs replacing.
1ǃThe system may have been over or under charged with gas, which can be judged through the pressure of the
measuring system.
2ǃThe shaft of compressor is seized and the compressor needs replacing.
<(6
12
The compressor is started normally, but
malfunctions are reported after it has run for some
time.
Malfunction unsolved