Service diagnosis  
 
Domestic Air Conditioner
 
6.3.9 Overheat Protection For Discharge Temperature 
Outdoor display:  LED1  flash 8 times 
 
Method of       
The Discharge temperature control is checked with the temperature being detected   
Malfunction      
by the Discharge pipe thermistor 
Detection 
Malfunction      
when the compressor discharge temperature is above 110ć
 
Decision 
Conditions    
Supposed         ■ 
Electronic expansion valve defective 
Causes           ■ 
 Faulty thermistor 
■  
Faulty PCB        
 
Troubleshooting    
* Caution 
  Be sure to turn off power switch before connect or disconnect connector,      or 
else parts damage may be occurred. 
 
 
 
 
Electrify the machine again and turn it on with the remote controller, 
then measure the temperature at the exhaust temperature sensor of 
the compressor on the outdoor unit 
The temperature exceeds 
110 ć  shortly after the 
machine starts u
? 
1) The cryogen may have been leaked during 
installation, or there may be leakage in the piping 
system. 
2) There may be other causes to make the exhaust 
temperature too high. 
Malfunctions occur after running for some time even 
though the measured temperature is below 110ć. Pull 
out the exhaust sensor and measure its resistance at 
standard temperatures according to the 
resistance-temperature table 
The results deviate 
much? 
The sensor is damaged. Replace the sensor 
with a new one. 
The outdoor mainboard is damaged and needs be 
re